2-68 PACSystems* RX3iPROFINET Controller Command Line Interface Manual July 2011 GFK-2572
2
show sm
Global Command
This command displays the PROFINET Controller / PLC backplane Shared Memory (SM) status
and counters.
show sm Command Format
show sm
Example
Screen Display
device-name> show sm
01-JAN-2000 00:06:38.0000
<<< Shared Memory Status >>>
Shared memory startup complete (07H)
Slave firmware version: 1.00
Master firmware version: 1.00
Shared memory heap status:
Heap memory size (bytes) = 16773120 (00FFF000H)
Slave heap size (bytes) = 8336896 (007F3600H)
Slave heap overhead (bytes) = 41216 (0000A100H)
Master heap size (bytes) = 8386560 (007FF800H)
Slave currently avail (bytes) = 8336896 (007F3600H)
Slave currently in use (bytes) = 0049664 (0000C200H)
Master currently avail (bytes) = 8386560 (007FF800H)
Master currently in used (bytes) = 0 (00000000H)
<<< Shared Memory Interface Counters >>>
IcRqRset=0000001cH IcHIPmsg=00000001H IcLOPmsg=00000000H IcTstInt=00000001H
IcSftRst=0000001bH IcMIntIn=00000001H IoScanPD=00000000H HpRlbSlv=00000000H
HpRlbMst=00000000H HpBBound=00000000H HpBogSlv=00000000H HpBogMst=00000001H
HpRsvBad=00000000H MbLoQput=00000003H MbHiQput=0001edcbH MbLoQget=00000003H
MbHiQget=00000004H
device-name>