Table4.4-T:V/fcurveselection(440V)-Sizes≥5300-4
Type Specification 01-00 V/f curve Type Specification 01-00 V/f curve
General purpose
50Hz
0
(Hz)
440
50
0
1.3
(0),(F)
17
2.5
30
High Starting Torque (*)
50Hz
Low
Starting
Torque
8
(Hz)
0
(9)
501.3
2.5
(8)
440
32
30.6
18
17
9
F
( 50Hz
Default
setting )
High
Starting
Torque
60Hz
60Hz
Saturation
1
(Hz)
440
0
(2)
(1),(F)
17
30
60Hz
Low
Starting
Torque
A
(Hz)
440
0
(B)
601.5
3
(A)
32
30.6
18
17
F
( 60Hz
Default
setting )
B
50Hz
Saturation
High
Starting
Torque
2
Variable torque
72Hz 3
(Hz)
72
0
(3)
601.5
3
17
30
440
Constant-power torque (Reducer)
90Hz C
(Hz)
440
90
(C)
60
0
1.5
17
3
30
50Hz
Variable
Torque 1
4
(Hz)
0
(5)
501.3 25
(4)
440
17
115
80
120Hz D
(Hz)
440
(D)
17
30
Variable
Torque 2
5
60Hz
Variable
Torque 3
6
(Hz)
0
(7)
601.5 30
(6)
440
17
115
80
180Hz E
(Hz)
440
1800
(E)
601.5
17
3
30
Variable
Torque 4
7
(*) Select high starting torque only for the following conditions.
(1) The power cable length is > 150m (492ft).
(2) Voltage drop at startup is high.
(3) An AC reactor is used on the input side or output side of the inverter.
(4) Motor power lower than the inverter rated
power.
130 VDI100 • Instruction manual