7. OperationMethodConguration(Run/Stop)
The inverter offers users several choices to run and stop from different sources. The most commonly used
methods are described in the next sections.
Operation command is selected with parameter 00-02.
00-02: Run Command Selection
This function sets the frequency command source.
Setting Range: 0 to 3
To set parameter 00-02:
- After power-up press the DSP/FUN key
- Set Group 00 (Basic Fun), and select parameter -02 with the UP/DOWN ▲ and ▼ keys and press the
READ/ ENTER key.
Code Parameter Name / Range
00-02 Main Run Command Source Selection
0: Keypad control
1: External terminal control
2: Communication control (RS-485)
3: PLC
7.1. Run/StopfromtheLED/LCDKeypad(00-02=0)
Use the RUN key to run the drive in forward direction and the FWD/
REV key to change the motor direction. (Note: to disable reverse
direction set parameter 11-01 to 1)
Press STOP key to stop the inverter. (Note: Stop method can be set
with parameter 07-09, default is deceleration to stop).
316 VDI100 • Instruction manual