EasyManuals Logo

gefran VDI100 Series User Manual

gefran VDI100 Series
362 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #267 background imageLoading...
Page #267 background image
The default values for the ASR can be used in most applications, no adjustment is required. Adjusting the
low-pass lter time and speed estimator gains requires a good understanding of the overall system. If a
high-speed system response in combination with stable operation is required consider using SLV or SV
control mode.
Parameter 20-15 sets the gain switch frequency at low-speed and parameter 20-16 sets the gain switch
frequency at high-speed.
Operating at a speed below 20-15 will result in a larger excitation current for low-speed operation accuracy.
When the frequency reference rises above 20-16, the inverter will output the rated excitation current at the
no-load voltage (02-19).
For general purpose applications parameter 20-15 should be set to a value of 5 ~ 50% of the motor base
frequency.
If this value is too high, the inverter output may saturate. Parameter 20-16 should be set to a value of 4Hz
or more above the value of 20-08.
When experiencing speed jitter at high speed and stable operation during mid-range speed while operating
a heavy load (>100%), it is recommended to reduce the no-load voltage (02-19) or tune the FOC parame-
ters (18-05 ~ 18-06).
Parameter 20-17 and 20-18 are for compensating speed feedback at low speed and high speed.
Use parameter 20-17 to adjust the torque compensation gain for the low speed range. By tuning 20-17an
offset is added to the torque-speed curve. Increase 20-17 when the no-load speed is lower than the fre-
quency reference. Decrease 20-17 when the no-load speed is higher than the frequency reference. The
effect on the torque-speed curve from 20-17 is shown as the following gure.
Figure4.4.115Effectonthetorque-speedcurvefrom20-17
Decrease 20-17 Increase 20-17
Torque
Speed
Use parameter 20-18 to adjust the torque compensation gain for middle to high speed range. For most
general purpose applications it is not necessary to adjust the 20-18. By tuning 20-18an offset is added to
the torque-speed curve. Increase 20-18 when the no-load speed is lower than the frequency reference.
Decrease 20-18 when the no-load speed is higher than the frequency reference. The effect on the torque-
speed curve from 20-18 is shown as the following gure 4.4.116.
Figure4.4.116Effectonthetorque-speedcurvefrom20-17
Torque
Speed
Decrease
20-18
Decrease
20-18
Increase
20-18
Increase
20-18
(1) ASR main delay time (20-08).
a) Does not required to be adjusted for general purpose applications
b) When the set value of 20-08 is set high, the speed response will and therefore system response will de-
crease improving system stability.
(2) ASR integral limit (20-04)
a) Setting a small value may prevent system response when the load suddenly changes.
VDI100 • Instruction manual 267

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran VDI100 Series and is the answer not in the manual?

gefran VDI100 Series Specifications

General IconGeneral
Brandgefran
ModelVDI100 Series
CategoryInverter
LanguageEnglish

Related product manuals