■ 08-06MotorOverloadOperationSelection
Code Parameter Name / Range
08-06 Start-up mode of overload protection operation (OL1)
0: Stop output after overload protection
1: Continuous operation after overload protection.
08-06=0: When the inverter detects a motor overload the inverter output is turned off and the OL1 fault mes-
sage will ash on the keypad. Press RESET button on the keypad or activate the reset function through the
multi-function inputs to reset the OL1 fault.
08-06=1: When the inverter detects a motor overload the inverter will continue running and the OL1 alarm mes-
sage will ash on the keypad until the motor current falls within the normal operating range.
VDI100 • Instruction manual 359