- Signal contact for smoke and heat extraction
The signal contact of a fire alarm system can be connected to terminals X12.1 and X12.2. This allows the door
to be used as a smoke and heat exhaust (SHE) in areas of up to 1600 m² (according to the Industrial Building
Directive). When an alarm occurs, the SHE position is approached regardless of the current door position. As
long as the signal contact is closed, all safety devices and command devices are without function, except for
the EMERGENCY STOP switch.
Mount the product according to the
manufacturer's instructions.
Set the SHE position with menu item 3.5 (min. 2.5
m).
Activate the function with option .8 in menu item
2.7 / 2.8.
4
3
12.112.2
BMA
i
Symbol for the activated SHE
X13 - Traffic lights for traffic control
You can connect two red / green traffic light pairs to terminals X13.1 to 13.6.
The door control has an integrated traffic light control to regulate the traffic. The traffic lights are supplied
with power either by X1 1.8/1.9 or externally. The external voltage supply requires a mains supply with
neutral.
i
We recommend using LED traffic lights.
Mount the product according to the
manufacturer's instructions.
13.1
13.213.3 13.413.5 13.6
13.113.1
1
2
1
11
2
2
2
1.9
1.8
1.9
1.9
1.8
1.8
Voltage supply over X1 1.8/1.9.
An external supply of voltage is possible.
Traffic lights (red/green) outdoors
Traffic lights (red/green) indoors