Select the actual mode for connecting the battery to the inverter. If there is
no battery connected in the system, it is unnecessary to configure the
battery model and working mode, and the equipment will operate in the
self-use mode by default.
Select the actual battery model.
Battery Type only supports: AGM/GEL/Wet Battery (Flooded).
Set parameters for lithium battery (GOODWE and third party battery)
Enable or disable SOC protection.
Depth Of Discharge (On-
Grid)
The maximum depth of discharge of the battery when the system is
working on-grid.
Depth Of Discharge (Off-
Grid)
The maximum depth of discharge of the battery when the system is
working off-grid.
The battery will be charged to preset SOC protection value by utility grid or
PV when the system is running on-grid. So that the battery SOC is
sufficient to maintain normal working when the system is off-grid.
Set parameters for lead-acid battery
Please set it according to the battery technical parameters.
The internal resistance of the battery. Please set it according to the battery
technical parameters.
By default, when the temperature is higher than 25℃, the upper limit of
charging voltage will decrease by 3mV for every 1℃ increase. The actual
settings should be based on the technical parameter of the battery.
Lower Limit Of Discharge
Voltage
Please set it according to the battery technical parameters.
Maximum Discharging
Current
Please set it according to the battery technical parameters. The greater the
discharge current is, the shorter the working time of the battery is.
The maximum current during charging, used to limit the charging current.
Please set it according to the battery technical parameters.