the corresponding inverter according
to its user manual.
3. Check whether the communication
connection of the equipment is
normal, with no loose, aging or wrong
connection, etc.
11.5.2.3 Battery fault (LX A5.0-30)
Alarm state
When the battery ALM indicator turns red, troubleshoot the issue by referring to the
SOC indicator's display status.
NO.
SOC indicator
Fault
Solutions
1
Battery
abnormality
Power off and wait for 2 hours. If
the problem persists, please
contact the after-sales service.
2
Abnormal
temperature
Turn off the device to wait for the
temperature to return to normal. If
the problem persists after
restarting, please contact the
after-sales service center.
3
Abnormal
current
Restart the battery. If the problem
persists, please contact the after-
sales service.
4
Balancing
fault
Power off and wait for 2 hours. If
the problem persists, please
contact the after-sales service.
5
Wire harness
exception
Restart the battery. If the problem
persists, please contact the after-
sales service.
6
Relay open-
circuit fault
Restart the battery. If the problem
persists, please contact the after-
sales service.