60
The power cable between batteries
The power cable between inverter and busbar
The power cable between battery and busbar
6.3.1 Preparing Breakers
Number
Circuit breaker
Recommended specifications
Comment
1
ON-GRID circuit
breaker
Nominal current 90A, nominal voltage
230V
Prepared by
customers.
2
Battery breaker
Optional in compliance with local laws
and regulations
GW8000-ES-C10: nominal current
200A, nominal voltage 60V
GW12K-ES-C10: nominal current
250A, rated voltage 60V
GW12K-ES-C10: nominal current
300A, rated voltage 60V
Prepared by
customers.
3
GEN breaker
GW8000-ES-C10: nominal current
≥63A, nominal voltage ≥230V
GW10K-ES-C10, GW12K-ES-C10:
nominal current 75A, nominal
voltage 230V
Prepared by
customers.
4
Off-grid load
breaker
Nominal current 90A, nominal voltage
230V
Prepared by
customers.
5
RCD
Optional in compliance with local laws
and regulations
Type A
ON-GRID RCD: 300mA
BACK-UP RCD: 30mA
Prepared by
customers.
6.3.2 Preparing Cables
Number
Cable
Recommended specifications
Obtain method
1
Inverter PE cable
Single-core outdoor copper cable
Prepared by

Table of Contents