Single-core outdoor copper cable
Wiring requirements for inverter
battery ports:
Conductor cross-sectional area:
70mm²
Outer diameter: 15.7mm-
16.7mm
Requirements for cables between
battery and busbar:
LX A5.0-10, cross sectional area
of conductor: 25mm²
LX A5.0-30, cross sectional area
of conductor: 50mm²
LX U5.0-30, cross sectional area
of conductor: 25mm²
Requirements for cables between
battery and battery:
LX A5.0-10, cross sectional area
of conductor: 25mm²
LX A5.0-30, cross sectional area
of conductor: 50mm²
LX U5.4-20, cross sectional area