Parallel communication port
Connect the inverter communication port
or battery parallel communication port
Communication port for parallel system
Communication port for parallel system
6.6.1 Connecting the Power Cable between the Inverter and Battery
Measure the DC cable using the multimeter to avoid reverse polarity connection. Also,
the voltage should be within the permissible range.
Connect the battery cables to the corresponding terminals such BAT+, BAT- and
grounding ports correctly. Otherwise it will cause damage to the inverter.
Ensure that the whole cable cores are inserted into the terminal holes. No part of the
cable core can be exposed.
Ensure that the cables are connected securely. Otherwise it will cause damage to the
inverter due to overheat during its operation.
Do not connect one battery pack to more than one inverter at the same time. Otherwise,
it may cause damage to the inverter.
Overview of inverter and battery power cable