After the function is enabled, the battery can be awakened when it
shuts down due to under-voltage protection.
Only applicable to lithium batteries without circuit breakers. After
being enabled, the output voltage of the battery port is around
60V.
9.4.4.2 Setting Lead-acid Battery Parameters
1. Before setting the parameters of lead-acid batteries, it is necessary to read the
user manual, technical parameters and other related materials of lead-acid
batteries. To ensure the safety of batteries, please strictly follow the relevant
materials of lead-acid battery manufacturers to set the battery parameters.
Otherwise, the risks caused thereby shall not be within the scope of the
responsibility of the inverter manufacturer.
2. The voltage range of lead-acid batteries needs to match the inverter, and the
recommended voltage of lead-acid batteries connected to the inverter is ≤60V,
otherwise the inverter may not operate properly.
3. The SOC of lead-acid batteries is calculated by the inverter BMS, not the actual
battery capacity, which may result in SOC value deviation or jump. SOC is only
used as a reference for battery capacity. Performing SOC value calibration after
the battery is fully charged can improve the accuracy of the SOC value.
This function supports settings through the SolarGo app or LCD screen.
Method I: Setting via SolarGo APP
Step 1: Enter the parameter settings interface through Home > Settings > Advanced
Settings > Battery Function.
Step 2: Enter the parameters and tap √. The parameters are set successfully.
Please set it according to the battery technical
parameters.
When the battery is approaching full charge, it
will switch to float charging mode. This value is
the upper limit of charging voltage in this mode.