174
F05:Grid 10 minutes
overvoltage
protection
range of safety
requirements.
automatically after detecting that the
utility grid is normal.
2. Check if the grid voltage is running at
a high voltage for a long time. If it
occurs frequently, please check if the
grid voltage is within the allowable
range.
Contact the local power company
if the grid voltage exceeds the
permissible range.
Modify the grid overvoltage rapid
protection threshold after
obtaining the consent of the local
power company if the grid voltage
is within the permissible range.
6
Grid Overfrequency/
F06:Grid
overfrequency
protection
Utility grid exception.
The actual grid
frequency exceeds the
requirement of the
local grid standard.
1. If the problem occurs occasionally, the
utility grid may be abnormal
temporarily. The inverter will recover
automatically after detecting that the
utility grid is normal.
2. If the problem occurs frequently,
check whether the grid frequency is
within the permissible range.
Contact the local power company
if the grid frequency exceeds the
permissible range.
Modify the overfrequency
protection threshold or disable the
overfrequency protection function
after obtaining the consent of the
local power company if the grid
frequency is within the permissible
range.
7
Grid
Underfrequency/
F07:Grid
underfrequency
protection
Utility grid exception.
The actual grid
frequency is lower
than the requirement
of the local grid
standard.
1. If the problem occurs occasionally, the
utility grid may be abnormal
temporarily. The inverter will recover
automatically after detecting that the
utility grid is normal.
2. If the problem occurs frequently,