GREE         U-Match 5 SERIES UNIT SERVICE MANUAL 
101 
(2)   Prepare relevant tools 
1)  Prepare nitrogen. Please strictly follow the nitrogen welding standards during the welding process. 
Make sure there is sufficient nitrogen. The nitrogen pressure should be above 2.0MPa; 
2)  Prepare welding rods. Prepare some welding rods of common specifications and some special 
welding rods that contain more than 5% silver. They are used to weld the compressor. The suction 
and exhaust openings of the compressor are all connected to copper-plated steel pipes, so we 
need to use special welding rods and solder; 
3)  Prepare applicable welding tools. Please evaluate how much oxygen and acetylene should be used 
according to the current welding condition. Try to avoid repeated welding. 
4)  Prepare a complete set of tools, including an internal hexagonal wrench, diagonal pliers, pincer 
pliers, nipper pliers, a universal meter, a pressure gauge, cross screwdriver, straight screwdriver, 
more than two wrenches, insulating tape and wire cables.   
Step 2: Disconnect power 
If the compressor needs to be replaced after judging as above, then switch off the outdoor unit and 
disconnect the power cable of the outdoor unit. Use insulating tape to wrap the power cable and put a notice 
board on the power switch to remind people to be cautious of electric shock.   
Step 3: Neaten the electric components 
When you detach the compressor wires, temperature sensors and electric heaters,  mark them 
correspondingly for the convenience of reconnecting them.   
Step 4: Discharge refrigerant 
Discharge refrigerant from the system. Discharge simultaneously from the high pressure side and low 
pressure side. Do not discharge too fast (It should take more than 12h to completely discharge the refrigerant); 
otherwise, large quantity of lubricant will escape from the system together with the refrigerant.   
Step 5: Detach the compressor   
WARNING 
(1)   The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware 
of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable 
refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe. 
(2)   Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A 
halide torch (or any other detector using a naked flame) shall not be used. 
Check the condition of the damaged compressor, including its position and model. 
If the information of the compressor is confirmed, check the oil quality. 
(a) If the oil is clear and impurities-free, we consider that the oil of the system is not polluted. Meanwhile, if