GREE         U-Match 5 SERIES UNIT SERVICE MANUAL 
12 
expansion valve will produce rattling sound. When cooling or heating mode is turned on, the valve will be open at 
a certain step before the compressor starts.   
2.2.1.3 Outdoor Fan Control 
This series air conditioner has two types of outdoor units: one with a single fan and the other with double 
fans. The outdoor fan can run at the highest level 10 and the lowest level 1. By controlling the speed of outdoor 
fan, the unit can achieve cooling at low temperature and heating at high temperature. In fan mode, outdoor fan 
will not work.   
2.2.1.4 4-way Valve Control 
After heating mode is turned on for a while, 4-way valve will be energized to change the direction of 
refrigerant flow so that the system can run in heating and the indoor unit will not blow cold air. Under other modes, 
the valve will not be energized.   
To avoid the 4-way valve from incorrectly changing directions, when the unit stops in heating, due to a 
temperature point or other protection reasons, the 4-way valve will continue to function temporarily and lose 
power after a while.   
There must be adequate differential pressure for the 4-way valve to change directions.   
2.2.2 Special Control 
2.2.2.1 Defrosting Control 
ODU defrosting control in heating: Defrosting will start when the temperature sensed by outdoor tube 
temperature sensor reaches a preset value. During defrosting, the 4-way valve will switch to the cooling condition, 
and outdoor and indoor fans will both stop. When the temperature sensed by outdoor tube temperature sensor 
reaches the preset value of defrosting stop, system will quit defrosting. The 4-way valve will switch back to the 
heating condition, outdoor fan will start working first and indoor fan will resume its previous fan speed after 
performing cold air prevention. 
2.2.2.2 Oil Return Control 
If the unit is running at low frequency for a long time, system will enable oil return control. This is to lead oil in 
the pipeline back to the compressor so that the compressor will not be lack of oil. Generally, the oil return takes 
about 5min. The compressor running frequency will be raised to the preset oil return frequency.   
2.2.2.3 Refrigerant Recovery Control 
Enabling method: Remote controller and wired controller both use the same enabling method. That is, within