GREE         U-Match 5 SERIES UNIT SERVICE MANUAL 
68 
Troubleshooting: 
Malfunction of 
discharge 
temperature 
sensor
Check if the 
discharge temperature sensor on 
mainboard is inserted on the 
needle stand correctly
Disconnect 
the temperature sensor and 
measure if its resistance is 
normal
Correctly insert the 
temperature sensor 
on the needle stand
Replace the 
temperature sensor
Replace the 
outdoor 
mainboard
Yes
No
No
Yes
 
Note: Please refer to Appendix 1 for the relation between temperature and resistance of temperature sensor. 
3.4.13 “F5” Wired Controller Temperature Sensor Error 
Error display: IDU wired controller and IDU receiver light board will display F5 
Error judgment condition and method: 
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the 
range of AD value, If the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report 
the error. 
Possible reason: 
■Poor contact between temperature sensor and terminal in mainboard interface 
■Temperature sensor is abnormal 
■Detecting circuit is abnormal 
Troubleshooting: 
Malfunction of 
wired controller 
temperature 
sensor
Replace the 
wired controller