GREE         U-Match 5 SERIES UNIT SERVICE MANUAL 
19 
displays setting state and press ▲ or ▼ button to adjust. There are 2 selections: 
(1)   Centralized controller (LCD displays 00). 
(2)   Long-distance monitoring (LCD displays 01). 
2.3.9.9 Selecting fan mode of indoor fan motor 
Under  debugging  state,  press  Mode  button  to  adjust  to  “11”  in  temperature  displaying  zone.  Timer  zone 
displays setting state and press ▲ or ▼ button to adjust.   
a.There are 5 selections for low static pressure duct: 
(1)   P3 (LCD displays 03). 
(2)   P4 (LCD displays 04). 
(3)   P5 (LCD displays 05). 
(4)   P6 (LCD displays 06). 
(5)   P7 (LCD displays 07). 
Note:
 You can select P03, P04, P05, P06, P07 in fan mode of indoor fan motor, which means different fan mode 
combinations are corresponding to different static pressure. Ex-factory defaulted mode is P05. You can set the 
mode through wired controller. S01, S02, S03……S12, S13 means the rotation speed of indoor unit is from low to 
high. 
Combination relationship of P03, P04, P05, P06, P07. 
Static 
pressure 
selection 
Super 
high 
speed 
High 
speed 
Medium 
high 
speed 
Medium 
speed 
Medium 
low speed 
Low 
speed 
Quiet 
R1 speed 
Quiet 
R2 speed 
Quiet 
R3 speed 
P03  S09  S08  S07  S06  S05  S04  S03  S02  S01 
P04  S10  S09  S08  S07  S06  S05  S04  S03  S02 
P05  S11  S10  S09  S08  S07  S06  S05  S04  S03 
P06  S12  S11  S10  S09  S08  S07  S06  S05  S04 
P07  S13  S12  S11  S10  S09  S08  S07  S06  S05 
b.There are 9 selections for high static pressure duct: 
(1)   P1 (LCD displays 01). 
(2)   P2 (LCD displays 02). 
(3)   P3 (LCD displays 03). 
(4)   P4 (LCD displays 04). 
(5)   P5 (LCD displays 05). 
(6)   P6 (LCD displays 06). 
(7)   P7 (LCD displays 07). 
(8)   P8 (LCD displays 08).