GREE         U-Match 5 SERIES UNIT SERVICE MANUAL 
63 
3.4.7 “E9” Water Overflow Protection 
Error display: IDU wired controller and IDU receiver light board will display E9 
Error judgment condition and method: 
Check the status of IDU float switch. When water level is too high, float switch is activated, so water full 
protection happens. 
Possible reason: 
■IDU is installed improperly 
■Drainage pump is broken 
■Float switch operates abnormally 
■IDU mainboard is abnormal; 
Troubleshooting: