GREE         U-Match 5 SERIES UNIT SERVICE MANUAL 
18 
indoor fan will start operation for a while and then stop if the indoor unit hasn’t met the startup conditions for 
15min. If the indoor unit still hasn’t met the startup conditions, the above-mentioned heat accumulation 
prevention control will cycled. 
Mode 2: After unit stops when reaching temperature point, the indoor fan motor stops operation with a 
10s-delay no matter in cooling mode or in heating mode. 
2.3.9.5 Mode selecting of compressor electric heating belt 
Under  debugging  state,  press  Mode  button to  adjust to “06”  in  temperature displaying  zone.  Timer  zone 
displays setting state and press ▲ or ▼ button to adjust. There are 2 selections: 
(1)   Mode 1 (LCD displays 00). 
(2)   Mode 2 (LCD displays 01). 
Note: 
Mode 1: Compressor electric heating belt starts when outdoor ambient temperature is below 35
℃
  and stops 
when outdoor ambient temperature is above 37
℃
. When outdoor ambient temperature is within 35
℃
  ~ 37
℃
, the 
belt will keep its previous operation state. 
Mode 2: Compressor electric heating belt starts when outdoor ambient temperature is below -2
℃
  and stops 
when outdoor ambient temperature is above 0
℃
. When outdoor ambient temperature is within -2
℃
  ~0
℃
, the 
belt will keep its previous operation state. 
2.3.9.6 Selecting low-power consumption mode 
Under  debugging  state,  press  Mode  button to  adjust to “07”  in  temperature displaying  zone.  Timer  zone 
displays setting state and press ▲ or ▼ button to adjust. There are 2 selections: 
(1)   With low-power consumption mode (LCD displays 00). 
(2)   Without low-power consumption mode (LCD displays 01). 
2.3.9.7 Selecting door control function 
Under debugging state, press  Mode  button to  adjust to “08”  in  temperature displaying  zone.  Timer  zone 
displays setting state and press ▲ or ▼ button to adjust. There are 2 selections: 
(1)   Without door control function (LCD displays 00). 
(2)   With door control function (LCD displays 01). 
2.3.9.8 Selecting long-distance monitoring or centralized controller 
Under  debugging  state,  press  Mode  button to  adjust to “10”  in  temperature displaying  zone.  Timer  zone