GREE         U-Match 5 SERIES UNIT SERVICE MANUAL 
20 
(9)   P9 (LCD displays 09). 
Note:
 You can select P01, P02, P03, P04, P05, P06, P07, P08, P09 in fan mode of indoor fan motor, which 
means different fan mode combinations are corresponding to different static pressure. Ex-factory defaulted mode 
is P05. You can set the mode through wired controller. S01, S02, S03……S12, S13 means the rotation speed of 
indoor unit is from low to high. 
Combination relationship of P01, P02, P03, P04, P05, P06, P07, P08, P09. 
Static 
pressure 
selection 
Super 
high 
speed 
High 
speed 
Medium 
high 
speed 
Medium 
speed 
Medium 
low speed 
Low 
speed 
Quiet 
R1 speed 
Quiet 
R2 speed 
Quiet 
R3 speed 
P1  S05  S03  S02  S02  S01  S01  S01  S01  S01 
P2  S06  S04  S03  S03  S02  S02  S02  S02  S02 
P3  S07  S05  S04  S04  S03  S03  S03  S03  S03 
P4  S08  S06  S05  S05  S04  S04  S04  S04  S04 
P5  S09  S07  S06  S06  S05  S05  S05  S05  S05 
P6  S10  S08  S07  S07  S06  S06  S06  S06  S06 
P7  S11  S09  S08  S08  S07  S07  S07  S07  S07 
P8  S12  S10  S09  S09  S08  S08  S08  S08  S08 
P9  S13  S11  S10  S10  S09  S09  S09  S09  S09 
2.3.9.10 Selecting compensation of temperature sensor at air return 
Under  debugging  state,  press  Mode  button to  adjust to “12”  in  temperature displaying  zone. Timer zone 
displays setting state and press ▲ or ▼ button to adjust. There are 16 selections: 
(1)   Compensate 0
℃
  (LCD displays 00). 
(2)   Compensate 1
℃
  (LCD displays 01). 
(3)   Compensate 2
℃
  (LCD displays 02). 
(4)   Compensate 3
℃
  (LCD displays 03). 
(5)   Compensate 4
℃
  (LCD displays 04). 
(6)   Compensate 5
℃
  (LCD displays 05). 
(7)   Compensate 6
℃
  (LCD displays 06). 
(8)   Compensate 7
℃
  (LCD displays 07). 
(9)   Compensate 8
℃
  (LCD displays 08). 
(10)   Compensate 9
℃
  (LCD displays 09). 
(11)   Compensate 10
℃
  (LCD displays 10).