GREE         U-Match 5 SERIES UNIT SERVICE MANUAL 
59 
Troubleshooting: 
E3 protection
Check if the 
system low 
pressure is lower 
than 0.05MPa
No
Yes
Charge 
refrigerant 
according to the 
requirement and 
then turn on the unit 
to see if E
3 
protection still 
occurs
Yes
Enter 
debugging mode 
through wired 
controller and select 
without refrigerant 
lacking protection; then 
turn on the unit to see 
if E3 protection still 
occurs
No
Completely open the liquid 
valve and gas valve of outdoor 
unit
Check if the liquid 
valve and gas 
valve of outdoor 
unit open 
completely
Yes
Yes
Yes
Weld the leakage point and 
recharge refrigerant after 
vacuum pumping and pressure 
retaining are passed
Check if there is 
leakage in the 
pipeline
Reconnect wire according to 
the circuit diagram or replace 
the pressure switch
Yes
35-85 outdoor units 
are without low pressure switch and 
check if the wiring of mainboard is 
normal;100-160 outdoor units are 
with low pressure switch and 
check if the low pressure 
switch and its wiring 
are normal
Replace the outdoor main 
control board
No
 
3.4.4 “E4” Compressor Air Discharge High-temperature Protection 
Error display: ODU mainboard, IDU wired controller and IDU receiver light board will display E4 
Error judgment condition and method: 
Test the compressor discharge temperature through compressor discharge pipe and shell top temperature 
sensor. If the tested temperature value is higher than 115℃, the unit will stop for protection