GREE U-Match 5 SERIES UNIT SERVICE MANUAL
21
(12) Compensate 11
(LCD displays 11).
(13) Compensate 12
(LCD displays 12).
(14) Compensate 13
(LCD displays 13).
(15) Compensate 14
(LCD displays 14).
(16) Compensate 15
(LCD displays 15).
Note:
Indoor ambient temperature compensation can be set through the wired controller (E.g.: If 02 is selected, it
indicates the compensation temperature is 2
. If the indoor ambient temperature detected by the temperature
sensor at air return is 29
, the ambient temperature after compensation is 29
-2
=27
).
After finishing setting, press Enter/Cancel button to save and exit setting. After entering this interface, the
system will exit this menu if there is no operation on the button within 20s. Normal off state interface will be
displayed and present setting will not be saved.
2.3.9.11 Auto mode selection
Under debugging state, press Mode button to adjust to “16” in temperature displaying zone. Timer zone
displays setting state and press ▲ or ▼ button to adjust. There are 2 selections:
(1) Auto mode 1, the set temperature under auto mode can’t be adjusted (LCD displays 01).
(2) Auto mode 2, the set temperature can be adjusted under auto mode (LCD displays 02).
2.3.9.12 Defrost mode selection
Under debugging state, press Mode button to adjust to “17” in temperature displaying zone. Timer zone
displays setting state and press ▲ or ▼ button to adjust. There are 2 selections:
(1) Defrost mode 1 (LCD displays 01).
(2) Defrost mode 2 (LCD displays 02).
2.3.9.13 Heat pump unit and cooling only unit selection
Under debugging state, press Mode button to adjust to “18” in temperature displaying zone. Timer zone
displays setting state and press ▲ or ▼ button to adjust. There are 2 selections:
(1) Heat pump type unit (LCD displays 00).
(2) Cooling only unit (LCD displays 01).
After finishing setting, press Swing/Enter button to save and exit setting. After entering this interface, the
system will exit this menu if there is no operation on the button within 20s. Normal off state interface will be
displayed and present setting will not be saved.