3.4.14 “C5” IDU Jumper Cap Error 
Error display: IDU wired controller and IDU receiver light board will display C5 
Error judgment condition and method: 
If jumper cap model doesn‘t match with mainboard, this error will be reported. 
Possible reason: 
■Jumper cap is not installed. 
■Jumper cap model is wrong. 
■Detecting circuit is abnormal. 
Troubleshooting: 
 
3.4.15 “EE” ODU Memory Chip Error 
Error display: IDU wired controller, IDU and ODU receiver light board will display EE 
Error judgment condition and method: 
If ODU mainboard cannot read the memory chip, this error will be reported.   
Possible reason: 
■ Memory chip on the ODU mainboard is damaged. 
■. Memory chip is weakly welded.   
■. Memory chip lead is short-circuited. 
Troubleshooting: 
Malfunction of ODU memory chip
error
Replace the outdoor
mainboard