Troubleshooting: 
 
3.4.36 “PU” Charge Loop Error 
Error display: ODU mainboard, IDU wired controller and IDU receiver light board will display PU 
Error judgment condition and method: 
When the charge loop starts to get charged and the busbar voltage cannot reach the set value in a certain 
period of time, then it can be judged that charge loop error exists. System will shut down for protection. 
Possible reason: 
■Voltage of power grid is abnormal. Voltage is too low. 
■Drive board charge loop element is abnormal. 
■Drive  board busbar  voltage sampling  circuit element  is  damaged or  drive  chip  busbar  voltage  sampling  AD 
terminal is abnormal. 
Troubleshooting: 
PU
Charge loop error
Normal protection
Replace the drive board
Grid voltage is too low ?
YES
NO