GREE         U-Match 5 SERIES UNIT SERVICE MANUAL 
15 
Pollution Level 
Accumulated 
Operating Time 
(hour) 
Pollution Level 
Accumulated 
Operating Time 
(hour) 
Pollution Level 
Accumulated 
Operating Time 
(hour) 
11  6000  21  1800  31  200 
12  6500  22  2200  32  300 
13  7000  23  2600  33  400 
14  7500  24  3000  34  500 
15  8000  25  3400  35  600 
16  8500  26  3800  36  700 
17  9000  27  4200  37  800 
18  9500  28  4600  38  900 
19  10000  29  5000  39  1000 
2.3.2 Low-temperature Drying Function 
Under dry mode, when the setting temperature is 16
℃
, press “▼” button for twice, the setting temperature 
becomes 12
℃
, then the unit enters into low-temperature dry function. 
When low-temperature dry function is turned on, directly press “▲” button or switch the mode can quit the 
function. 
2.3.3 Child-lock Function 
Without error, under ON or OFF status of unit, press “▲” and “▼” buttons simultaneously for 5 seconds can 
enter into child-lock function, the liquid crystal screen will display “
”; Press “▲” and “▼” buttons simultaneously 
again for 5 seconds can quit the child-lock function. 
Under child-lock status, no response for pressing any buttons. The unit will memorize the child-lock status 
after power failure and re-energizing the unit. 
2.3.4 Memory Function 
Under power-off status, press “MODE” and “▲” button simultaneously for 5 seconds can turn on or turn off 
memory function. When memory function is set, “MEMORY” displays. 
If memory function has not been set, when the unit is re-energized after power failure, the unit is power-off 
status. If the memory function is set in wired controller, when the wired controller is re-energized after power 
failure, it will resume to the operating status before power failure. 
2.3.5 Door Control Function 
When door control function is selected, the wired controller will work when the room card is inserted and stop