219 
2. Temperature/Pressure List of Refrigerant 
R32 
Pressure  Temperature 
 
Pressure  Temperature 
 
Pressure  Temperature 
Kpa 
℃ 
Kpa 
℃ 
Kpa 
℃ 
100  -51.909  1250  14.153  2400  38.688 
150  -43.635  1300  15.52  2450  39.529 
200  -37.323  1350  16.847  2500  40.358 
250  -32.15  1400  18.138  2550  41.173 
300  -27.731  1450  19.395  2600  41.977 
350  -23.85  1500  20.619  2650  42.769 
400  -20.378  1550  21.813  2700  43.55 
450  -17.225  1600  22.978  2750  44.32 
500  -14.331  1650  24.116  2800  45.079 
550  -11.65  1700  25.229  2850  45.828 
600  -9.1503  1750  26.317  2900  46.567 
650  -6.8046  1800  27.382  2950  47.296 
700  -4.5925  1850  28.425  3000  48.015 
750  -2.4975  1900  29.447  3050  48.726 
800  -0.50613  1950  30.448  3100  49.428 
850  1.393  2000  31.431  3150  50.121 
900  3.2092  2050  32.395  3200  50.806 
950  4.9506  2100  33.341  3250  51.482 
1000  6.624  2150  34.271  3300  52.15 
1050  8.2352  2200  35.184  3350  52.811 
1100  9.7896  2250  36.082  3400  53.464 
1150  11.291  2300  36.965  3450  54.11 
1200  12.745  2350  37.834  3500  54.748 
3. Refrigerant Notice/Concentration 
This air conditioner uses R32 refrigerant. The construction area for installation, operation and storage of the 
air conditioner must be larger than the minimum construction area. The minimum area for installation is 
determined by: 
1.Refrigerant charging quantity for the entire system (ex-factory charging quantity + additional charging 
quantity); 
2.Checking out in the applicable tables: 
(1)   For indoor unit, confirm the model of indoor unit and check the corresponding table. 
(2)   For outdoor unit that is installed or placed indoors, select the corresponding table according to the height 
of the room. 
Height of the room  Select the applicable table 
<1.8m 
Floor standing type 
≥1.8m  Wall mounted type