GREE         U-Match 5 SERIES UNIT SERVICE MANUAL 
72 
Troubleshooting: 
Outdoor heat exchanger is blocked
Indoor heat exchanger is blocked.
Ambient temperature is out of the
operation range
H
4
Overload
Too much charging quantity.
Error still exists?
Remove the obstacle
Remove the obstacle
Normal protection. No
need to handle it.
Release a proper amount
of refrigerant
Replace the drive board
Replace the compressor
YES
YES
YES
YES
YES
NO
NO
NO
NO
 
3.4.19 “H5” IPM Protection 
Error display: ODU mainboard, IDU wired controller and IDU receiver light board will display H5 
Error judgment condition and method: 
When power is connected and drive chip received IPM lead F0 that is of low level, than it is IPM module 
malfunction. System will shut down for protection. 
Possible reason: 
■Compressor 3-phase wire connection is lack of phase or phase-reversed. 
■System is overloaded and compressor current is too large.   
■Drive board IPM module is damaged.   
■Drive board IPM module’s 15V power supply is lower than 13.5V. 
■Drive board 6-line PWM signal and the corresponding element are abnormal.   
■Drive board compressor current sampling circuit element is damaged or drive chip current sampling AD terminal 
is abnormal.   
■Compressor is damaged.