GREE         U-Match 5 SERIES UNIT SERVICE MANUAL 
23 
Point 3 for the setting method. The address mode is defaulted to be connecting to centralized controller mode 
and the defaulted address is 1.   
When the centralized controller is connected, centralized controller of the unit can be realized to control unit 
ON/OFF, operation mode, set fan speed/temperature and weekly timer.   
(3)   Setting method of centralized controller for up to 36 indoor units: 
Firstly, set the address mode of wired controller into Long-distance control address mode. The setting 
method is:   
Under off state of the unit, press Function and Timer buttons at the same time for 5s to go to the debugging 
menu. Press Mode button to adjust to “10” in temperature displaying zone. Timer zone displays setting state and 
press ▲ or ▼ button to adjust. There are 2 selections:   
A. Centralized controller address mode (LCD displays 00).   
B. Long-distance control address mode (LCD displays 01).   
Choose the second selection and then press Swing/Enter button to save and exit setting. Now, the address 
of wired controller is set to match the address of centralized controller. The unit will memorize this setting status. 
The setting value will be memorized after power failure.   
Address setting of each unit: when the address mode is set to be Long-distance control address mode. The 
address setting value range is 01~36. The setting method is:   
Under off state of the unit, press Function and Mode buttons at the same time for 5s to enter setting interface 
of  wired  controller  address.  LCD  displays  address  sequence.  Press  ▲  or  ▼  button  to  adjust  the  address 
sequence and then press Swing/Enter button to confirm. The setting value will be memorized after power failure.   
When the address is set, the wired controller can be removed and connect the centralized controller to the 
indoor mainboard. Then connect the required units to realize centralized control of these units. 
Note:   
①
 The unit addresses in the same network must be different, otherwise, communication malfunction will 
occur and the unit can not work normally. 
②
 When centralized controller is to be connected, the unit address range is 1-36. Only 36 sets of unit in 
maximum can be connected. 
③
 The code and model of wired controller is as below:   
Name  Product code  Remark 
Centralized controller 
CE52-24/F(C) 
MC207052 
Only 36 sets of unit in maximum can be 
connected to this controller