press ▲ or ▼ button to adjust. There are 2 selections: 
1) Centralized controller address mode (LCD displays 00) 
2) Long-distance control address mode (LCD displays 01) 
Choose the second selection and then press Swing/Enter button to save and exit setting. Now, the address 
of wired controller is set to match the address of long-distance control. The unit will memorize this setting status. 
The setting value will be memorized after power failure. Address setting of each unit: when the address mode is 
set to be long-distance control address mode. The address setting value range is 01~255. The setting method is: 
Under off state of the unit, press Function and Mode buttons at the same time for 5s to enter setting interface 
of wired controller  address.  LCD  displays  address  sequence.  Press  ▲  or  ▼  button  to  adjust  the  address 
sequence and then press Swing/Enter button to confirm. The setting value will be memorized after power failure. 
Notes: 
①
 In order to realize the MODBUS interface function, the address mode of the unit must be set into 
long-distance control address mode; You can not set it into centralized control address mode, otherwise, 
this function can not be realized. 
②
 The unit can not be connected to MODBUS and centralized controller at the same time; Only one of them 
can be selected. 
③
 255 sets of unit in maximum can be connected in the same network; The unit addresses in the same 
network must be different, otherwise, the unit control will be affected. 
④
 Perform wiring when the unit power is cut off.