GREE U-Match 5 SERIES UNIT SERVICE MANUAL
25
press ▲ or ▼ button to adjust. There are 2 selections:
1) Centralized controller address mode (LCD displays 00)
2) Long-distance control address mode (LCD displays 01)
Choose the second selection and then press Swing/Enter button to save and exit setting. Now, the address
of wired controller is set to match the address of long-distance control. The unit will memorize this setting status.
The setting value will be memorized after power failure. Address setting of each unit: when the address mode is
set to be long-distance control address mode. The address setting value range is 01~255. The setting method is:
Under off state of the unit, press Function and Mode buttons at the same time for 5s to enter setting interface
of wired controller address. LCD displays address sequence. Press or button to adjust the address
sequence and then press Swing/Enter button to confirm. The setting value will be memorized after power failure.
Notes:
In order to realize the MODBUS interface function, the address mode of the unit must be set into
long-distance control address mode; You can not set it into centralized control address mode, otherwise,
this function can not be realized.
The unit can not be connected to MODBUS and centralized controller at the same time; Only one of them
can be selected.
255 sets of unit in maximum can be connected in the same network; The unit addresses in the same
network must be different, otherwise, the unit control will be affected.
Perform wiring when the unit power is cut off.