70
Analog inputs, AI
Voltage signal ranges:
0.5 - 3.5 VDC, AL AU.
0-5 VDC, AU.
0-10 VDC, AU.
Voltage signal: R
i
greater than 100 kΩ at 25 °C.
Leak currents may occur at high operating
temperatures. Keep the source impedance low.
Current signal ranges:
0-20 mADC, AU.
4-20 mADC, AL AU.
Current signal: R
i
is equal 292 Ω.
Current overload protection: Yes. Change to voltage
signal.
Measurement tolerance: - 0/+ 3 % of full scale
(maximum-point coverage).
Screened cable: 0.5 - 1.5 mm
2
, 28-16 AWG.
Maximum cable length: 500 m excluding
potentiometer.
Potentiometer connected to +5 V, GND, any AI:
Use maximum 10 kΩ.
Maximum cable length: 100 m.
Analog output, AO
Current sourcing capability only.
Voltage signal:
Range: 0-10 VDC.
Minimum load between AO and GND: 1 kΩ.
Short-circuit protection: Yes.
Current signal:
Ranges: 0-20 and 4-20 mADC.
Maximum load between AO and GND: 500 Ω.
Open-circuit protection: Yes.
Tolerance: - 0/+ 4 % of full scale (maximum-point
coverage).
Screened cable: 0.5 - 1.5 mm
2
, 28-16 AWG.
Maximum cable length: 500 m.
Pt100/1000 inputs, Pt
Temperature range:
Minimum: -30 °C. 88 / 882 .
Maximum: 180 °C. 168 / 1685 .
Measurement tolerance: ± 1.5 °C.
Measurement resolution: less than 0.3 °C.
Automatic range detection, Pt100 or Pt1000: Yes.
Sensor fault alarm: Yes.
Screened cable: 0.5 - 1.5 mm
2
, 28-16 AWG.
Use Pt100 for short wires.
Use Pt1000 for long wires.
LiqTec sensor inputs
Use Grundfos LiqTec sensor only.
Screened cable: 0.5 - 1.5 mm
2
, 28-16 AWG.
Grundfos Digital Sensor input and output, GDS
Use Grundfos Digital Sensor only.
Power supplies
+5 V:
Output voltage: 5 VDC - 5 %/+ 5 %.
Maximum current: 50 mADC (sourcing only).
Overload protection: Yes.
+24 V:
Output voltage: 24 VDC - 5 %/+ 5 %.
Maximum current: 60 mADC (sourcing only).
Overload protection: Yes.
Digital outputs, relays
Potential-free changeover contacts.
Minimum contact load when in use: 5 VDC, 10 mA.
Screened cable: 0.5 - 2.5 mm
2
, 28-12 AWG.
Maximum cable length: 500 m.
Bus input
Grundfos GENIbus protocol, RS-485.
Screened 3-core cable: 0.5 - 1.5 mm
2
, 28-16 AWG.
Maximum cable length: 500 m.

Table of Contents

Other manuals for Grundfos CME

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos CME and is the answer not in the manual?

Grundfos CME Specifications

General IconGeneral
Liquid temperature range0 °C to +60 °C
Maximum operating pressure10 bar
SeriesCME
Frequency50/60 Hz
Max Pressure10 bar
Pump TypeCentrifugal
MaterialStainless steel
Applicationspressure boosting, irrigation
Pumped liquidClean water
ApprovalsCE
Max Liquid Temperature60°C
Power Supply1-phase or 3-phase