Appendix
74
Electrical connection
Conductors
See section 7.2 Cable requirements, page 11.
Torques
Maximum tightening torques for the terminals can be
found in section Torques, page 71.
Line reactors
Maximum line reactor size must not exceed 1.5 mH.
Short circuit current
If a short circuit occurs, the pump can be used on a
mains supply delivering not more than 5000 RMS
symmetrical amperes, 600 V maximum.
Fuses
Fuses used for motor protection must be rated for
minimum 500 V.
Motors up to and including 10 hp require class K5
UL-listed fuses. Any UL-listed fuse can be used for
motors of 15 hp.
Branch circuit protection
When the pump is protected by a circuit breaker, this
must be rated for a maximum voltage of 480 V. The
circuit breaker must be of the "inverse time" type.
Overload protection
Degree of overload protection provided internally by
the drive, in percent of full-load current: 102 %.

Table of Contents

Other manuals for Grundfos CME

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos CME and is the answer not in the manual?

Grundfos CME Specifications

General IconGeneral
Liquid temperature range0 °C to +60 °C
Maximum operating pressure10 bar
SeriesCME
Frequency50/60 Hz
Max Pressure10 bar
Pump TypeCentrifugal
MaterialStainless steel
Applicationspressure boosting, irrigation
Pumped liquidClean water
ApprovalsCE
Max Liquid Temperature60°C
Power Supply1-phase or 3-phase