EasyManuals Logo

Grundfos CUE Series User Manual

Grundfos CUE Series
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
13
6.3 Connecting the signal terminals
Connect the signal cables according to the guidelines for good
practice to ensure EMC-correct installation. See section
6.6 EMC-correct installation.
Use screened signal cables with a conductor gauge size of
min. 22 AWG and max. 16 AWG.
Use a 3-conductor screened bus cable in new systems.
6.3.1 Wiring diagram, signal terminals
Fig. 21 Wiring diagram, signal terminals
Terminals 27, 29 and 37 are not used.
6.3.2 Minimum connection, signal terminals
Operation is only possible when the terminals 18 and 20 are
connected, for instance by means of an external on/off switch or
ashort wire.
Fig. 22 Required minimum connection, signal terminals
Caution
As a precaution, signal cables must be separated
from other groups by reinforced insulation in
their entire lengths.
Note
If no external on/off switch is connected, short-
circuit terminals 18 and 20 using a short wire.
TM03 8800 2507
+24 V out
+24 V out
DI 2
DI 3
DI 4
GND
GND
AO 1
+10 V out
Ext. setpoint
Sensor 1
GND
RS-485 GND Y
RS-485 A
RS-485 B
0/4-20 mA
1 K
0-20 mA
0/4-20 mA
0-10 V0-10 V
Start/stop
Terminals
53 and 54:
See section
6.3.5
Terminal Type Function
12 +24 V out Supply to sensor
13 +24 V out Additional supply
18 DI 1 Digital input, start/stop
19 DI 2 Digital input, programmable
20 GND Ground for digital inputs
32 DI 3 Digital input, programmable
33 DI 4 Digital input, programmable
39 GND Ground for analog output
42 AO 1 Analog output, 0-20 mA
50 +10 V out Supply to potentiometer
53 AI 1 External setpoint, 0-10 V/0/4-20 mA
54 AI 2 Sensor input, sensor 1, 0/4-20 mA
55 GND Ground for analog inputs
61 RS-485 GND Y GENIbus, GND
68 RS-485 A GENIbus, signal A (+)
69 RS-485 B GENIbus, signal B (-)
Note
The RS-485 screen must be connected to ground.
TM03 9057 3207
Start/stop
GND
Grundfos.bk Page 13 Friday, July 30, 2010 10:10 PM

Table of Contents

Other manuals for Grundfos CUE Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos CUE Series and is the answer not in the manual?

Grundfos CUE Series Specifications

General IconGeneral
CategoryDC Drives
Output Voltage24 V DC
Control Signal0-10 V, 4-20 mA
CommunicationModbus RTU
Protection FeaturesOvervoltage, overcurrent, overtemperature, short circuit
Humidity5% to 95% (non-condensing)
Enclosure classIP20
Enclosure RatingIP20

Related product manuals