Chapter 7 Function for protection
61
Err-7
Abnormity of
drive stop
The input terminals of CCW,
CW drive stop are both broken
off.
Check the connection and
power supply of input
terminals.
Encoder connection is
wrong.
Check the connection.
Encoder is damaged. Change the motor.
Encoder cable is inferior. Change the cable.
Err-9
Photoelectric
encoder signal
fault
Encoder cable is so long
that the encoder voltage is
too low.
Shorten the cable.
Employ with multi-core
parallel power-up.
Control power supply
voltage input is too low.
Check the control power
supply.
Err-10
Control power
supply
undervoltage
Internal connector
assembly of driver is
inferior.
Switch power supply is
abnormal.
Chip is damaged.
Change the driver.
Check the connector
assembly.
Check the switch power
supply.
Occurring in switching
on control power
supply
Circuit board is at fault Change the servo driver.
Power-up voltage is low.
Overheated.
Check the driver.
Power on again.
Change the driver.
Driver U, V, W terminals are
short circuit.
Check the connection.
Earthing is not well done.
Be grounded correctly.
Motor insulation is
damaged.
Change the motor.
Err-11 IPM module
fault
Occurring in motor
running
It is interfered with.
Add the circuit filter.
Be far away from the
interference source.
Driver U, V, W terminals are
short circuit.
Check the connection.
Earthing is not well done. Be grounded correctly.
Motor insulation is damaged. Change the motor.
Err-12 Over-current
Driver is damaged. Change the driver.