GSK CNC Equipment Co., Ltd.
62
Occurring in switching
on control power
supply
Circuit board is at fault. Change the servo driver.
The motor runs exceeding
rated torque.
Check the load.
Reduce the start-stop
frequency.
Reduce the torque limit
value.
Change the driver and
motor with the larger power
ones.
Hold brake is not on. Check the hold brake.
Motor vibrates unsteadily.
Adjust the gain.
Increase the acceleration/
deceleration time.
Reduce the load inertia.
Err-13 Overload
Occurring in motor
running
One of U, V, W phases is
broken off.
The connection of encoder
is mistaken.
Check the connection.
Occurring in switching
on control power
supply
Circuit board is at fault. Change the servo driver.
Brake resistance connection
is broken off.
Connect the wire again.
Brake transistor is
damaged.
Internal brake resistance is
damaged.
Change the servo driver.
Err-14
Brake circuit
fault
Occurring in motor
running
Brake loop capacity is not
enough.
Reduce the start-off
frequency.
Increase the acceleration/
deceleration time constant.
Reduce the torque limit
value.
Reduce the load inertia.
Change the driver and
motor with larger power
ones.