EasyManua.ls Logo

GW Instek APS-1102A - Example of Sequence Operation Settings; Figure 4-13. Step Transition Example (During AC+DC-INT Mode); Table4-12. Program Settings

GW Instek APS-1102A
285 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
APS-1102A User Manual
APS-1102A
4-40
4.4.6 Example of sequence operation settings
The following describes the steps for setting a new sequence operation, based on the sequence transition
example described in Table4-12. The time unit is seconds (s). ( See 5.6.5 Time unit setting to
change the time unit.)
Figure 4-13. Step Transition Example (during AC+DC-INT mode)
Table4-12. Program Settings
Step Number
1
2
3
4
5
6
Step time (TIME)
0.1
0.2
0.1
0.2
0.2
0.3
DC voltage (DC VOLT)
25. 0
75. 0
75. 0
50. 0
100. 0
0.0
DC voltage operation type
SWEEP
KEEP
CONST
SWEEP
SWEEP
SWEEP
Step end (STEP TERM)
CONT
CONT
CONT
CONT
CONT
STOP
Jump step (JUMP STEP)
0
0
0
2
0
0
Jump times (JUMP NUM)
1
1
1
1
1
1
Branch 0 (BRANCH0)
0
0
0
0
6
0
Though the DC voltage of step 2 is set to 75.0 V, the output DC voltage will be 25.0 V which is succeeded
from the previous step (step 1) because the DC operation type of step 2 is set to KEEP. After executing
step 4, the sequence will jump to step 2 because the jump step of step 4 is set to 2 (<1> in Figure 4-13).
The output DC voltage will be kept to 50.0 V coming from the previous step (step 4) because the DC
operation type of step 2 is set to KEEP. The jump times of step 4 is set to 1, so the sequence will move to
the next step (= step 5) after jumping once and executing step 4 (<2> in Figure 4-13). The step time of
step 5 is set to 0.2 s and the branch 0 jump step of step 5 is set to step 6, so the sequence will immediately
move to step 6 when the branch 0 is input within the step time (<3> in Figure 4-13).
Step 1
(0.1 s)
Step 2
(0.2 s)
Step 3
(0.1 s)
Step 4
(0.2 s)
Step 2
(0.2 s)
Step 3
(0.1 s)
Step 4
(0.2 s)
Step 5
(0.2 s)
Step 6
(0.3 s)
<1>
<2>
<3>
Time
Jump to step 2
KEEP setting
is valid.
Jump to step 6
upon branch 0.
100.0 V
75.0 V
50.0 V
25.0 V
0.0 V
Output
voltage
Step 5 setting
value
Branch 0 input
Sequence start

Table of Contents