MODEL 50 CONTROLLER INSTALLATION AND COMMISSIONING INSTRUCTIONS
19
31-00233-02
Figure 15: RS485-1 three-position slide switch setting MID
Figure 16: RS485-1 three-position slide switch setting BIAS
Figure 17: RS485-1 three-position slide switch setting END
NOTE
All terminals are protected (up to 24 VAC) against short-circuiting and incorrect wiring
except when the 3-position slide switch is set to "END," in which case the terminals of the
RS485-1 bus (24, 25, and 26) have no such protection. Higher voltages may damage the
device.
According to BACnet standards, a minimum of one and a maximum of two BACnet devices
must have its/their bias resistors switched ON. In the case of the RS485-1 interface of the
CIPer Model 50, setting its slide switch to either "BIAS" or "END" fulfills this requirement.
47 kOHM
47 kOHM
+5VISO
GND-1
RS485-1 (+)
RS485-1 (-)
25
26
MID (DEFAULT)
END
BIAS
MID
550 OHM
550 OHM
+5VISO
GND-1
RS485-1 (+)
RS485-1 (-)
25
26
BIAS
END
BIAS
MID
550 OHM
150 OHM
550 OHM
+5VISO
GND-1
RS485-1 (+)
RS485-1 (-)
25
26
END
END
BIAS
MID