MODEL 50 CONTROLLER INSTALLATION AND COMMISSIONING INSTRUCTIONS
31-00233-02
8
System Overview
Overview of Hardware
Table 3. Overview of models (hardware)
Feature
Description
Max. cable
length
Order No
Without HMI
With HMI
WEB-
EHSERIESNX26ND
WEB-
EHSERIESNX26D
UI
NTC10k (Type II) / NTC20k (Type II) /
0…10V / slow BI, 0.4 Hz
1200 ft
(366 m)
8
8
NTC10k (Type II) / NTC20k (Type II) /
0…10V fix pull-up / slow BI, 0.4 Hz
1200 ft
(366 m)
2
2
BI
Open = 24 V / closed 2.0 mA / totalizer 15
Hz
1200 ft
(366 m)
4
4
AO
0..11 V (max. 1 mA)
1200 ft
(366 m)
4
4
BO
Relay N.O. contact: 3 A, 250 VAC, 30 VDC
1200 ft
(366 m)
4
4
Relay N.O. contact (high in-rush): 10 A,
250 VAC, 30 VDC
1200 ft
(366 m)
1
1
Relay N.O. contact with one common: 3 A,
250 VAC, 30 VDC
1200 ft
(366 m)
3
3
Total I/Os
--
26
26
Bus
interfaces
RS485-1, isolated, BACnet MS/TP, Panel
Bus, or Modbus RTU Master or Slave
communication
1)
3600 ft
(1097 m)
1
1
RS485-2, non-isolated, BACnet MS/TP,
Panel Bus, or Modbus RTU Master or
Slave communication (NOTE: It is
imperative that the RS485-2 be powered
by a power supply having the proper
polarity. Failure to do so will make data
transmission impossible.)
1)
3600 ft
(1097 m)
1
1
Ethernet Interfaces (e-mail
communication, browser access, BACnet
IP communication, Niagara Network,
Modbus TCP)
300 ft
(91.44 m)
2
2