EasyManua.ls Logo

Honeywell CIPer 50 - Dual Ethernet Interface; Separated Network Configuration

Honeywell CIPer 50
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CIPer
TM
MODEL 50 CONTROLLER INSTALLATION AND COMMISSIONING INSTRUCTIONS
17
31-00233-02
To ensure that the discovery of devices, datapoints, schedules, and histories does not fail, you should enter a
gateway address. If there is no gateway address physically given by the Network Setting, then enter a gateway
address that relates to the IP address of the enabled Ethernet Interface. In Figure 11 the gateway address is
192.168.1.1, hence the IP address of Ethernet adapter 1 must be in the range of 192.168.1.2 to
192.168.1.255.
Default IP Addresses of Ethernet Interfaces 1 and 2
In any case, the default IP address of Ethernet interface 1 is: 192.168.200.20, mask 255.255.255.0
and the default IP address of Ethernet interface 2 is:192.168.201.20, mask 255.255.255.0
LEDs
The CIPer Model 50 controller features the following LEDs:
Figure 12: CIPer Model 50 controller LEDs
Table 4. CIPer Model 50 controller LEDs
Symbol
Color
Function Description
L1
Yellow
Lit = Daemon starting; flashing = station starting; if L2 is also flashing, then the
station has started.
L2
Yellow
Lit = platform has started / is reachable; flashing = station has started / is
reachable.
Tx
Yellow
RS485-1 status LED indicating transmission of communication signals.
Rx
Yellow
RS485-1 status LED indicating reception of communication signals.
Red
Indicates an active alarm; is controlled by WEBs- Alarm System; is configurable.
Green
Power LED.
See also section "CIPer Model 50 Controller Troubleshooting, Pg. 67 for a detailed description of the
behaviors of the LEDs and their meanings.
RS485 Interfaces
General
The CIPer Model 50 controller features two RS485 interfaces:
RS485-1 (consisting of push-in terminals 24 [GND-1], 25, and 26) is isolated and can be used for any
RS485-based communication protocol available within WEBs- Ecosystems, E.g: Panel Bus, BACnet MS/TP,
etc.
RS485-2 (consisting of push-in terminals 29, 30, and 31 [GND-2]) is non-isolated (i.e. GND-2 is internally
connected with terminal 1 [24V~0]) and can be used for any RS485-based communication protocol available
within WEBs- Ecosystems, e.g.: Panel Bus, BACnet MS/TP, etc.
NOTE
It is imperative that the RS485-2 be powered by a power supply having the proper polarity. Failure to do so
will make data transmission impossible.
L1 L2
Tx Rx
!
!

Table of Contents

Other manuals for Honeywell CIPer 50

Related product manuals