EasyManua.ls Logo

Honeywell CIPer 50 - Connecting Ciper Model 50 Via RS485-2 Interface to a Bacnet MS;TP Bus

Honeywell CIPer 50
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CIPer
TM
MODEL 50 CONTROLLER INSTALLATION AND COMMISSIONING INSTRUCTIONS
57
31-00233-02
Connecting CIPer Model 50 via RS485-2 Interface to a BACnet MS/TP Bus
NOTE
With regards to Figure 50 and Figure 51, please note the following:
Always power each CIPer Model 50 controller and the connected BACnet MS/TP modules
via separate transformers.
For "L," see section "RS485 Standard".
If any of the devices are electrically isolated, it is recommended that those devices be
connected to signal ground. See section "RS485 Standard".
Between devices equipped with non-isolated RS485 bus interfaces, potential differences
of max. ±7 V are allowed. Further, this bus should not extend beyond a single building.
Example 1: Single CIPer Model 50 Controller and Connected BACnet Modules (with inserted termination
resistor)
Figure 48: Connection of a single CIPer Model 50 controller via its RS485-2 interface to a BACnet MS/TP
Bus
The termination resistor must be inserted directly into the terminals of the last BACnet MS/TP module.
Example 2: Multiple CIPer Model 50 Controllers and Connected BACnet Modules
Figure 49: Connection of multiple CIPer Model 50 controllers via their RS485-2 interfaces to a BACnet
MS/TP Bus

Table of Contents

Other manuals for Honeywell CIPer 50

Related product manuals