EasyManua.ls Logo

Honeywell CIPer 50 - Field Devices; Routing Cables to Field Devices

Honeywell CIPer 50
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CIPer
TM
MODEL 50 CONTROLLER INSTALLATION AND COMMISSIONING INSTRUCTIONS
31-00233-02
52
Field Devices
Depending on the distance from the controller, field devices can be supplied with power by the same
transformer used for the Panel Bus I/O Modules, or by a separate transformer, using cables as specified in
Table 22.
Table 22. Power / communication cable specifications
Type of signal
Cross-sectional area
328 ft (100 m) (Figure 27) Power
supply via Panel Bus I/O Module
1312 ft (400 m) (Figure 26) Power
supply via a separate transformer
24 VAC power
16 AWG (1.5 mm
2
)
not allowed for >328 ft (100 m)
0…10 V signals
28 14 AWG (0.081 2.08 mm
2
)
For wiring field devices, see section “Powering Panel Bus I/O Models and Field Devices".
Routing Cables to Field Devices
Route low-voltage signal and output cables to field devices separately from mains cables.
Table 23. Minimum distances to power mains cables
Cable
Minimum Distance
shielded
0.4(10 mm)
unshielded
4(100 mm)
All low-voltage signal and output cables should be regarded as communication circuits in accordance with
VDE 0100 and VDE 0800 (or NEC or other equivalent).
If the general guidelines for cable routing are observed, it is not necessary to shield field device signal and
power supply cables.
If for whatever reason, the routing guidelines cannot be observed, the field device signal and power supply
cables must be shielded.
Shielding of cables leading to field devices must be grounded only at one end.
Do not connect the shield to the CIPer Model 50 controller.

Table of Contents

Other manuals for Honeywell CIPer 50

Related product manuals