MODEL 50 CONTROLLER INSTALLATION AND COMMISSIONING INSTRUCTIONS
31-00233-02
26
Configuring Ports to Enable Webserver Functions
The CIPer Model 50 controller provides webserver functionality, e.g., for using the WEBs N4 Supervisor. In
order to use webserver functions, the http and https standard port settings must be changed as follows:
http standard port 80 to 8080
https standard port 443 to 8443
After the changes are done, the controller is reachable via both pairs of ports, i.e., via the old standard ports
and via the newly set ports.
Procedure
1.
In the WEBs N4 Nav tree, expand the Services folder, and then double-click
WebService
.
RESULT: The Property Sheet displays to the right.