TM
MODEL 50 CONTROLLER INSTALLATION AND COMMISSIONING INSTRUCTIONS
25
31-00233-02
Configure the network as desired by applying the available options displayed.
To reset the controller to factory defaults, press F in the Boot menu.
ATTENTION: Resetting the controller to its factory defaults will result in the following:
The station will be deleted.
The platform credentials will be deleted.
The IP settings will be reset to the factory defaults (see section "Default IP Addresses of Ethernet
Interfaces 1 and 2").
RECOMMENDATION: Before leaving (closing) the terminal program, go to "Network Setup" and enter the
desired IP settings.
Reset the controller by entering Y.