MODEL 50 CONTROLLER INSTALLATION AND COMMISSIONING INSTRUCTIONS
55
31-00233-02
BACnet MS/TP Bus Connection
The CIPer Model 50 controller features two RS485 interfaces to which BACnet MS/TP devices can be
connected: RS485-1 (consisting of push-in terminals 24 [GND-1], 25, and 26) and/or RS485-2 (consisting
of push-in terminals 29, 30, and 31 [GND-2]).
NOTE
GND-2 is internally connected with 24V-0 (terminal 1)
BACnet MS/TP Bus Considerations
RS485-1 (isolated)
Max. BACnet MS/TP bus length: 3600 feet (9.6 78.8 kbps) or 2400 feet (115.2 kbps) (see also
section "RS485 Standard" ).
Use only shielded, twisted-pair cable and daisy-chain topology.
Must conform to EIA-RS485 cabling guidelines (see section "EIA 485 Cable Specifications").
RS485-2 (non-isolated)
Max. BACnet MS/TP bus length: 3600 feet (9.6 78.8 kbps) or 2400 feet (115.2 kbps) (see also
section "RS485 Standard" ).
Use only shielded, twisted-pair cable and daisy-chain topology.
Ground noise should not exceed the EIA-485 common mode voltage limit.
Must conform to EIA-RS485 cabling guidelines.
Should not extend beyond a single building.
Connecting CIPer Model 50 via RS485-1 Interface to a BACnet MS/TP Bus
NOTE
For Figure 45a and Figure 47, please note the following:
Always power each CIPer Model 50 controller and the connected BACnet MS/TP modules
via separate transformers.
For "L," see section "RS485 Standard“.
If any of the devices are electrically isolated, it is recommended that those devices be
connected to signal ground. See section "RS485 Standard".
Example 1: Single CIPer Model 50 Controller and Connected BACnet Modules (with inserted termination
resistor)
Figure 45; Connection of a single CIPer Model 50 controller via its RS485-1 interface to a BACnet MS/TP
Bus
The termination resistor must be inserted directly into the terminals of the last BACnet MS/TP module.