CIPer
TM
MODEL 50 CONTROLLER INSTALLATION AND COMMISSIONING INSTRUCTIONS
31-00233-02
54
Figure 43: IF-LON2
Depending upon the chosen network configuration, one or two terminations may be required.
The following LONWORKS termination module is available:
LONWORKS connection / termination module (mountable on DIN rails and in fuse boxes), order no. XAL-
Term2
Figure 44: LONWORKS connection and termination module
LONWORKS TERMINATION
PLUG-IN JUMPER
FTT/LPT
FREE TOPOLOGY:
52.3 OHM
100 μ
100 μ
52.3 Ohm
1
2
FTT/LPT
BUS TOPOLOGY:
105 OHM
100 μ
100 μ
105 Ohm
1
2
1
5
2
3
4
6
3
1
5
6
2
4
REMOVABLE SCREW-TYPE
2-POLE TERMINAL BLOCK
FTT/LPT BUS FTT/LPT FREE
PARK POSITION
(NO TERMINATION)