MODEL 50 CONTROLLER INSTALLATION AND COMMISSIONING INSTRUCTIONS
31-00233-02
60
Example: CIPer Model 50 Modbus Master Controller and Connected Modbus Slaves (with inserted
termination resistor)
Figure 51: Connection of an CIPer Model 50 Modbus master controller via its RS485-2 interface to a
Modbus with slaves
The termination resistor must be inserted directly into the terminals of the last Modbus slave.
NOTE
In this example, a maximum of one of the Modbus RTU slaves can be an CIPer Model 50 Modbus
RTU slave which must then be positioned at the end of the Modbus (as "Modbus Module #N");
the insertion of the aforementioned termination resistor is then unnecessary.