EasyManua.ls Logo

Honeywell ECS Series - Wiring SD Detectors; Addressing SD Devices; Heat or Smoke Detector Connection to the FACP; IDP or SK SLC Device Addressing Using Rotary Dials

Honeywell ECS Series
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LS10143-001SK-E IDP, SK, SD and SWIFT™ SLC Device Installation
7-8
in Figure 7-4.
Figure 7-4 IDP or SK SLC Device Addressing Using Rotary Dials
7.8 Wiring SD Detectors
The information in this section applies to SD Detectors.See Table 7-3 for P/N’s.
To Wire SD Detectors
1. Wire device bases as shown in Figure 7-5.
2. Set the address for each device as described in Section 7.9.
Figure 7-5 Heat or Smoke Detector Connection to the FACP
7.9 Addressing SD Devices
This section explains how to address SD detectors and modules. See Table 7-3 for a list of SD devices.
An access code with the option to set SLC Device Address enabled is required to perform this task.
To address a SD detectors:
Example 2: Device Set to 105.
All dials labeled for ONES
or TENS position.

Table of Contents

Other manuals for Honeywell ECS Series

Related product manuals