LS10143-001SK-E Programming
9-8
Template Override is shown when set to Yes.
Dynamic Activation -Is shown if a non-voice group is assigned to a Select/Dynamic Activation switch
number
Dynamic Activation / Template Override Cadence. (This is shown when the Template override is set to Yes
and Dynamic Activation is Yes): this setting sets the cadence of the non-voice group mapped to voice select
switch when activated using dynamic activation or by a template. See Sections 11.2.3.2 and 9.4.3 for more
information.
Defining Output Group Type
Each output group is defined as either a voice output group or a non-voice output group. Output points that are
audio circuits (all circuits on the ECS-50W, ECS-125W, ECS-DUAL50W, ECS-INT50W and ECS-CE4) can
only be assigned to voice output groups. Output points that are non-voice circuits (all other points and circuits
that are on all modules except the ECS-50W, ECS-125W, ECS-DUAL50W, ECS-INT50W and ECS-CE4) are
assigned to non-voice output groups.
Each of the output groups defined as voice can be mapped to a particular switch and LED on the ECS-VCM/
ECS-NVMC, ECS-RVM and ECS-SW24. This allows the user to see the state of the voice groups assigned to the
switches.
This also lets the user individually select which areas they want to do a live page into. Output groups not defined
as voice groups can also be assigned to these switches as long as there is a voice group already assigned to the
group. This allows for dynamically activating/deactivating both voice and strobes/other outputs in an area with a
single button press. See 11.2.3.2.
Figure 9-3 Corresponding Key and LED for Mapping Output Groups
Silencing Options
The following silencing options are available for each output group.
Table 9-3: Silencing Options
Optional
Timers
Description
Silence Inhibit Timed Silence after Inhibit. If this option is selected, the output group must be audible for a programmed
number of minutes before it can be silenced. If the condition that caused the output to activate has not
cleared during the time-frame, the output can be silenced. If you select this option, select the timeframe in
the delay field. Range is 0-60 minutes.
Auto Silence Silenceable. The output group will automatically silence after the timer expires. Range is 0-60 minutes.
ECS User Interface
ECS-SW24
Corresponding
Key and LED Numbers
Corresponding
Key and LED Numbers

Table of Contents

Other manuals for Honeywell ECS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ECS Series and is the answer not in the manual?

Honeywell ECS Series Specifications

General IconGeneral
BrandHoneywell
ModelECS Series
CategoryConference System
LanguageEnglish

Related product manuals