Model IFP-2100/ECS Installation Manual LS10143-001SK-E
7-11
7.10 Wiring the WIDP-WGI or SK-WGI
Note: The WIDP-WGI or SK-WGI, as part of the wireless network, has been tested for compliance with the Fed-
eral Communications Commission (FCC) requirements of the United States Government. It has not been
evaluated for use outside the USA. Use of this system outside the USA is subject to local laws and rules to
which this product may not conform. It is the sole responsibility of the user to determine if this product may
be legally used outside the USA.
Note: It is recommended to use the same wire gauge is there are multiple connections to the same terminal.
For more information regarding Gateway wiring instructions, see SWIFT manual LS10036-000FH-E or
LS10036-000SK-E.
7.10.1 Power Connections for the Gateway
The WIDP-WGI or SK-WGI, Wireless Gateway acts as a bridge between a group of wireless fire devices and a
SLC loop on the IFP-2100/ECS. It is powered by the SLC loops or by a regulated, external 24 VDC UL listed
power supply. See Table 7-4 for available wireless devices & modules. For details about wireless devices, system
setup, and operation, see the SWIFT
Smart Wireless Integrated Fire Technology Instruction Manual P/N
LS10036-000FH-E if using IDP or P/N LS10036-000SKFL-E for SK.

Table of Contents

Other manuals for Honeywell ECS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ECS Series and is the answer not in the manual?

Honeywell ECS Series Specifications

General IconGeneral
BrandHoneywell
ModelECS Series
CategoryConference System
LanguageEnglish

Related product manuals