Honeywell ECS Series - Panel to SK-NIC Connection; To Mount the SK-NIC Remotely

Honeywell ECS Series
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Model IFP-2100/ECS Installation Manual LS10143-001SK-E
5-5
2. Use the 6-pin cable included with SK-NIC to connect the IFP-2100/ECS to the SK-NIC. Connect the SK-
NIC to the pin connector on the control panel labeled Data Network. See Figure 5-6.
Figure 5-6 Panel to SK-NIC connection
3. Each SK-NIC has the ability to monitor for earth ground faults on the twisted pairs connected to Port 1 of its
terminal block TB2. Earth fault detection for any wiring at Port 2 of TB2 is done at the next/previous SK-
NIC due to these wiring connections being connected to Port 1 of TB2 at the next/previous SK-NIC.
4. Unused optic ports on fiber loop modules must have their dust caps placed on the port.
5. Based on the type of data medium chosen, run the twisted pair wiring/fiber optic cable to the next SK-NIC
using a class B or class A wiring method. A combination of both medium types can be used. See Figure 5-7,
Figure 5-8, Figure 5-9, and Figure 5-10 for SK-NIC wiring examples.
To mount the SK-NIC remotely:
Follow the steps above except; The 6-pin cable that runs from the SK-NIC to the IFP-2100/ECS, must be run in
conduit. See Figure 5-1.