Model IFP-2100/ECS Installation Manual LS10143-001SK-E
10-19
To access the F-Key Recording menu:
1. From the idle screen, press and hold the F-Key for 5 seconds.
2. Enter a PIN with F-Key macro recording privileges, if prompted.
10.9.1 Recording an F-Key Macro
1. Access the F-Key Recording menu and select the ‘Start FKEY Recording’ option.
2. The panel will return to the idle screen. Notice the 4th line on the display now alternates with <F# Key
Recording>, where # is the number of the F-Key being recorded.
3. Any Disabling or Activating of points, output groups, or templates from the site at this point will be pro-
grammed into the macro. Do this by going to any annunciator within the site and entering Main Menu ->
Point Functions and use Disable/Enable Point or use I/O Point Control to: disable output groups or individ-
ual points, or activate individual points.
4. Once you are finished with disabling or activating points/output groups, enter the F-Key Recording Menu
again and select the ‘End F-KEY Recording’ option.
5. The panel will return to the idle screen.
10.9.2 Aborting an F-Key Macro Recording Session
1. After an F-Key macro recording session has been started, the session can be canceled at any time by access-
ing the F-Key Recording menu and selecting ‘Abort F-KEY Recording’ option.
2. The panel will return to the idle screen.
10.9.3 Erasing an F-Key Macro
1. If an F-Key macro has already been recorded, you can erase it by accessing the F-Key Recording menu and
selecting the ‘Erase F-KEY Macro’ option.
2. The panel will return to the idle screen.
10.9.4 Using a Recorded F-Key Macro
1. From the idle screen on any annunciator in the site, press the F-Key you want to activate.
2. Once finished, to de-activate the macro press the F-Key again.
10.9.5 F-Key Status Event
When an F-Key is enabled, it activates its corresponding F-Key Active event. This is a status type event that can
activate outputs without showing any status on annunciator displays. This should be used for ancillary purposes
only.
10.9.6 F-Key Map Inhibit
The F-Keys have the ability to disable event - output group mapping for the purpose of simulating that the map
doesn’t exist. This can be setup to allow for testing purposes where notification of an entire building is not
desired during the test. This option is programmable for each output group map through HFSS Honeywell Fire
Software Suite.
When an F-Key is active and a map in the system is set to be disable by Map Inhibit, the system will show a
trouble event indicating it as such.

Table of Contents

Other manuals for Honeywell ECS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ECS Series and is the answer not in the manual?

Honeywell ECS Series Specifications

General IconGeneral
BrandHoneywell
ModelECS Series
CategoryConference System
LanguageEnglish

Related product manuals